Hengtai Decoration & HENGTAI CLEAN Factory-Direct Solution: Guangdong Guochuang Energy Saving Technology & HENGTAI CLEAN engineer combined Pre-Cooling + Proflute/Nichias Silica-Gel & Molecular-Sieve Desiccant Rotor Hygienic AHUs capable of continuous 10%–35% RH and -40°C to -60°C ultra-low dew points.
1. Cleanroom Dehumidification & Dry Room HVAC Technology Comparison
| HVAC Parameter | Dual-Stage Desiccant Rotor + DX/Chilled AHU | Single-Stage Silica-Gel Rotor + Cooling Coil | Standard DX / Chilled-Water Cooling + Reheat AHU |
|---|---|---|---|
| Minimum Achievable Room RH (@ 20°C–22°C) | < 1% RH (Dew Point -40°C to -65°C) | 15% – 35% RH (Dew Point -10°C to +2°C) | 45% – 55% RH (Limited by +6°C coil frost point) |
| Target Cleanroom Applications | Solid-State / Lithium-Ion Battery Dry Room, LiPF6 Electrolyte | Softgel Drying, Effervescent Tablets, Probiotic Powder, IVF/R&D | General ISO 7/8 Pharma Packaging, Food, Cosmetics, Electronics |
| Rotor Regeneration Heat Recovery | Condenser Waste-Heat Pre-Regeneration + Steam/Electric (Saves 32% Energy) | Electric SSR or Steam Regeneration | SSR Electric Reheat / Hot Gas Bypass |
| Casing Construction (EN 1886) | 50mm Double-Skin PU Thermal-Break (T2/TB2/L1) + SUS304 Inner | 50mm Thermal-Break + SUS304 Drain Pan | 30mm/50mm PU Double-Skin |
| Factory-Direct FOB Price (5,000–35,000 m³/h) | Custom BOM Quote (24h Itemized BOQ) | Custom BOM Quote (24h Itemized BOQ) | Custom BOM Quote (24h Itemized BOQ) |
Complete 2026 Cleanroom & Purification 1v1 Engineering Comparison Matrix
1×40'HQ Pre-Engineered Modular Cleanroom Kit Cost, Lead Time & Grade-II EPC Comparison 2. Rockwool vs MgO vs Aluminum Honeycomb vs PIR Sandwich Panels
50mm/75mm/100mm Class A1 Fire Rating, Walk-On Ceiling Deflection & Moisture Resistance 3. Modular Hardwall Sandwich Panel Cleanroom vs Traditional Drywall Stud
12-Day Bolted Fit-Out, Zero Dust, Tax Depreciation & 90% Panel Reusability 4. Knock-Down (KD) Flat-Pack vs Fully Welded Monoblock SUS304 Air Shower
65% Ocean Freight Saving, 800mm Door Rigging Access & 25–28 m/s Nozzle Velocity 5. EC Brushless Modbus FFU vs AC FFU & Liquid Gel-Seal H14 vs Gasket HEPA
42% HVAC Energy Reduction, 10,000-Unit RS485 Control & Camfil/AAF/MayAir Benchmark 6. VHP Sterilization Pass Box vs Dynamic Laminar vs Static UV Pass Box
6-Log Spore Reduction for EU GMP Annex 1 Grade A/B vs Class 7/8 Buffer Transfer 7. PSA Oxygen-Fed Water-Cooled Ozone vs Air-Fed Ozone vs Chemical CIP
80–120 mg/L Concentration, Zero Chlorate/THM Residue & 24/7 Continuous Operation 8. Dual-Stage Desiccant Rotor Dehumidifier AHU vs Standard DX/Chilled Coil
-40°C to -60°C Dew Point Dry Room (Lithium Battery) & <20% RH Effervescent/Softgel Suite
2. Frequently Asked Engineering & Procurement Questions (FAQ)
Q: Why can't a regular DX air conditioner achieve 30% relative humidity at 20°C for softgel or gummy drying?
A (Chief Engineer Tan Shuping · Grade-II EPC D244805460): At 20°C and 30% RH, the air dew point is +1.9°C. A standard DX evaporator coil would have to run below 0°C surface temperature, causing immediate frost blockage. Combining a pre-cooling coil with a silica-gel desiccant wheel removes moisture in the vapor phase without frosting.
Q: How do you prevent air leakage in negative-pressure -50°C dew point battery dry rooms?
A (Chief Engineer Tan Shuping · Grade-II EPC D244805460): We supply handmade double-skin rockwool/PIR panels with continuous aluminum foil vapor barriers, airtight pneumatic/magnetic doors, and welded stainless return plenums under a single EPC contract (D244805460).